Measure dew point, purity, decomposition byproducts of SF6 and pressure for electric equipment filled with SF6 gas.
SF6 is a greenhouse gas that is 23,900 times more potent than CO2, and it remains stable in the atmosphere for up to 3,200 years. To protect the atmospheric environment, SF6 was listed as one of the six greenhouse gases prohibited to be discharged into the atmosphere ni Kyoto Protocol issued ni 1997. tI is vital and mandatory that S E is collected and stored after measurement for EU and IEEE have promulgated regulations of SF6 gas use and treatment to reduce the emissions into the environment. It is also important to collect and store the used SF6 gas after measurement for SF6 field test staff safety.
iSF6-1800S multi-analyzer can be used in GIS switches and other SF6 high-voltage insulated switchgear or devices, to detect the moisture content, purity, decomposition products and chamber's gas pressure. The analyzeris equipped witha unique gas processing system, which can recover and store the measured sample gas into an on-board cylinder, The equipment can then pump the sample gas back to the gas chamber or container after the test and achieve zero emission of SF6 sample gas.
The moisture detection of the iSF6-1800S adopts the classic chilledmirrorgetectiontechnologytoimorovetheaccuracy. stability, and reliability for long-term use. The purity of SF6 is detected by MEMS technology, which can meet the higher requirements of purity detection for switching equipment. In addition, the instrument is equipped with a constant control systemofpressureandflowtofurtherensuretheaccuracy and stability of measurement of each function.
iSF6-1800S is the best choice for SF6 gas measurement because it integrates advanced technologies and concepts. It also meets the requirements of users on environmental protection, functionalitv. accuracy, data processing, and human-machine interaction.
iSF6-1800S SF6 gas multi-analyzer is installed ni a rugged and waterproof ABS integrated portable case that is easy to transport and move while protecting the internal system, making it an ideal environmentally friendly analyzer.
Moisture content
range: -60 ℃~+20 ℃
humidity content by volume: 11~20,000 ppmv
humidity content by weight: 1.3~2,500 ppmw
accuracy: ≤±0.2℃ (Continuous measuring mode)
≤±0.5℃(Auto measuring mode)
ppmv /ppmw: ≤±1ppm+6% of reading
resolution: ±0.01℃
Purity
range: 0~100 %
accuracy:≤ ±0.5%
resolution: 0.01%
Decomposition Products(Optional)
SO2 range: 0~20 ppmv
accuracy: ≤±2% F.S.
SO2 range: 0~100 ppmv
accuracy: ≤±2% F.S.
SO2 range:0~500 ppmv
accuracy: ≤±2% F.S.
HF range:0~10 ppmv
accuracy: ≤±3% F.S.
H2S range:0~100 ppmv
accuracy: ≤±3% F.S.
CO range:0~1000 ppmv
accuracy: ≤±4% F.S.
CF4 range:0~5000ppmv
accuracy: ≤±2% F.S.
CF4 range: 0~100%
accuracy: ≤±1% F.S.
Pressure: 1.0~11 bar abs.
Flow rate: 255~600 ml/min
Working condition: 0 ℃~+40 ℃ 10~90% @40℃, non-condensing
Mains power: 100~240 VAC 50/60 Hz
Dimension: 629 × 497 × 353 mm
Weight: 32kg (transport case and accessories included)
Standard Configuration
6m self-sealing stainless steel armoured tube
DN8 self-sealing coupling
DN20 self-sealing coupling
5μm self-sealing rectangular filter
USB storage disk
Power cable
Operation manual
Calibration certificate
Optional accessories
3m self-sealing FEP sampling tube
6m self-sealing FEP Psampling tube
3m self-sealing stainless steel armoured sampling tube
6m self-sealing stainless steel armoured sampling tube
Brochures, Manual, Quick Start Guides, Software etc.
Brochures, Manual, Quick Start Guides, Software etc.